Vertiv expands 800 VDC portfolio for AI data centres
The portfolio spans three deployment tiers—rack, pod, and data hall—with solutions from medium voltage to compute racks.
www.vertiv.com

Vertiv has added 800 VDC systems aimed at the AI compute pod and data hall, expanding an offering begun in May 2026 with the Vertiv™ PowerDirect 5000 Power Rack to cover deployments at the rack, compute pod, and data hall levels. This expansion allows operators to address the growing power requirements of AI data centres and scale their infrastructure as compute loads evolve, in a landscape where alternating current (AC) and direct current (DC) architectures will coexist across different timelines and risk tolerances.
Scott Armul, Chief Product and Technology Officer at Vertiv, noted that the 800 VDC power chain forms a set of system architectures and designs requiring power conversion and storage, distribution, protection, controls, and safety to be brought together through a holistic approach with safety built in by design for DC operation.
800 VDC architectures at rack, compute pod, and data hall levels
Vertiv structures its 800 VDC portfolio across three configurations tailored to existing facilities, mixed AC and DC environments, or campus-scale greenfield builds:
- 800 VDC to the rack: the Vertiv™ PowerDirect 5000 (±400 / 800 VDC) Power Rack sits beside the IT rack, supports up to 800 kW from 480 VAC, and integrates 30 hot-swappable 30 kW power units with battery backup providing at least 50 seconds of runtime. Inside the rack, the 1U Vertiv™ PowerDirect 3000 90 kW, 19" 800 VDC Power Shelf steps 800 VDC down to 54 VDC for compute racks, with up to 98.5% peak efficiency and support for 180% pulses for 0.5 milliseconds. By moving power conversion and storage outside the IT rack, this architecture frees up 8 to 16 rack units to add compute capacity.
- 800 VDC to the AI compute pod: the Vertiv™ PowerDirect 9000, 1.5 MW 800 VDC Power Center converts 480 VAC to 800 VDC for a row or pod and distributes power via the Vertiv™ PowerBar Track system and tap-off boxes to PowerDirect 3000 modules in each rack. It scales in 60 kW increments with 27 hot-swappable units and links to the Vertiv™ EnergyCore Li5 800 VDC battery cabinet (200 kW continuous backup and up to 98% efficiency, with up to six cabinets in parallel).
- 800 VDC to the data hall: the Vertiv™ PowerNexus MV SST, 5 MW 800 VDC solid-state transformer performs direct single-stage conversion from medium voltage to 800 VDC with galvanic isolation and up to 98% AC-to-DC efficiency. In an outdoor liquid-cooled container format, one unit can support a 4.8 MW superpod reference architecture, supports bidirectional flow, and coordinates with external storage via a DC/DC converter to absorb rapid AI load fluctuations.
Architectural flexibility, DC safety, and phased deployment
The portfolio centres on three pillars: architectural flexibility across rack, pod, or data hall; coordinated end-to-end integration (conversion, storage, distribution, protection, controls, and monitoring); and DC-specific safety measures, including touch-safe busbars, high-voltage isolation, mid-point grounding, ground-fault detection, and arc-flash prevention.
Kyle Keeper, Senior Vice President of the power management business unit at Vertiv, highlighted that having rack, compute pod, or data hall options enables operators to tailor deployment to their current infrastructure and power requirements while scaling their AI infrastructure. Pilot programmes, technical validations, and collaborative customer initiatives are currently under way.
Additional Context:
This section explains general principles of high-voltage direct current (HVDC) distribution and solid-state transformers in high-density data centres not included in the original release.
In traditional data centre distribution chains, power passes through multiple stages of voltage transformation and AC-to-DC rectification—from medium voltage to low-voltage distribution, power distribution units (PDUs), rack power supplies, and on-board converters—before reaching processors. Each additional stage introduces switching and conduction losses, while requiring more technical room space and distribution switchgear.
Unlike conventional iron-core and copper-winding transformers operating at mains frequency (50 or 60 Hz), a solid-state transformer (SST) uses high-frequency power electronics converters and a high-frequency isolation transformer. This design reduces magnetic volume, enables active voltage control and bidirectional power flow, and supports direct galvanic isolation between medium voltage and 800 VDC buses.